eurogard DIN-rail modems

the solution for all communication tasks in the industrial area, analog 33.6 and 56k, ISDN or GSM

 

 

Hutschienen-ModemsKey functions

The INSYS DIN-rail modems offer solutions for all communication tasks in the industrial area. The narrow DIN-housings, the 10 to 80V operating voltage and terminal strips for telephone and special functions guarantee problem-free installation in any switchboard.

  • 56k
  • ISDN
  • GSM
  • TCP/IP
  • Leased-Line, according to your requirements.

All modem types comply with international standards. They have all necessary certifications of the German Telekom and a Europe-wide CTR 21 certification.
The modems are addressed with the standard AT-commands or via V.25bis.
The error correction method MNP 2-4 or V.42 LAP-M and data compression V.42bis and MNP5 guarantee problem free and safe FAX- (Cl. 1-3) and data connections.
Please note the eurogard specials:

Remote configuration
Change modem and ISDN-settings via telephone
WatchDog
The watchdog function automatically carries out a reset when necessary
Alarm input
Transmission of up to 10 messages stored in the modem via SMS, fax and email, carried out by means of an external contact
Alarm output
Remote access to a relais output in the modem via SMS
Security Callback and password protection
Guarantee protection of your data, no access without password
Automatic log in with GSM
The GSM modems for mobile data-transmission log in automatically and monitor the connection to the mobile network

 

Hutschiene GSM
At a glance
  • Industrial modems with universal characteristics
  • Analog with 33.6 or 56k as well as leased- line
  • ISDN and GSM- (D1 and D2) version available
  • May be used for all data communication tasks
  • Europe-wide certification with BTZ-Nr. and CTR 21

eurogard offers industrial modems for all areas of data communication:

  • Facility automation and management
  • Environmental technologies
  • Suppliers
  • Energy management
  • PC-remote maintenance
  • Logistics

 

Technical specifications

 

Ordering information FMA 1033, FMA 1156 FMT 3001 FMG 4001 FME 10ETH
Network interface Analog tel. network ISDN S0/I.Euro ISDN GSM network Ethernet, 10 Base T
Data transmission rate 14.400bps - 56 kbps 64 kbps bis 14.400 bps 10 Mbps
Alarm inputs 2 2 2 2
Control outputs 2 (relay) 2 (relay) 2 (relay) 2 (relay)
Watchdog yes yes yes yes
Software Update Flash Flash Flash Flash
Galvanic isolation to telephone network to ISDN network - to Ethernet
Approvals R&TTE, CTR21, UL1)* R&TTE, CTR 3 R&TTE, CTR31, CTR32 -
Connection auto answer mode, sleep mode, idle connection control auto answer mode, sleep mode, idle connection control automatic GSM reconnection after power down, time-scheduled disconnection and reconnection, voice connection, SMS send/receive Automatic network connection, static IP address
Alarm function SMS2)*/Fax transmission, set up data connection, alarm transmission over data connection, pulsed alarm input: 11 SMS messages to 11 recipients, triggered by alarm input or AT command SMS2)* transmission, set up data connection,  alarm transmission over data connection, triggered by alarm input or AT command SMS, Fax2)* or email transmission2)*, set up data connection, alarm transmission over data connection, pulsed alarm input: 20 SMS messages to 20 recipients, establish voice connection, alarm input or AT command E-Mail transmission, triggered by alarm input or AT command
Control output AT command (local and remote) and per DTMF AT command (local and remote), connection status AT command (local and remote), SMS reception, alarm state, ring signal, GSM connection loss and per DTMF AT command (local and remote)
Security functions
password protected connection, security callback and remote control
caller ID (CLIP) protected data connection, caller ID (CLIP) protected security callback, password protected remote control
password protected data connection, security callback, remote control and password protected control by SMS
Data format 7O1, 7E1, 7N2, 7O2, 7E2, 8N1, 8O1, 8E1, 8N2 7O1, 7E1, 7N2, 7O2, 8N1, 8O1, 8E1, 8N2 7O1, 7E1, 7N2, 8N1, 8O1, 8E1 7O1, 7E1, 7N2, 7O2, 7E2, 8N1, 8O1, 8E1, 8N2
Protocols / Error correction V.32 bis, V.32, V.23, V.22, V.22bis, V.21, Bell Norm 103, 212 MNP2-4,Fax class 1/2 only 1056k: V.90 only 1056k and 1033: V.34+, V.34 B-Kanal: V.110, X.75, PPP, V.120, X.25, X31, Hdlc Transparent, V.42, LAPM, MNP 10, MNP 5D-Kanal 1TR6, DSS1, X.31 TS11, TS12, TS21, TS22, TS23, TS62 Fax class 3 8S24/25/26 Non transparent mode, V.42bis, V.110 ARP, ICMP, TCP/IP, UDP/IP, SMTP (send)

 

Electrical features

 

Power supply 10...80 VDC 10...80 VDC 10...80 VDC 10...80 VDC
Power consumption 2,5 W 1,25 W 3 W 2 W
Interface to application RS232, 9-pin SUB-D-jack RS232, 9-pin SUB-D-jack RS232, 9-pin SUB-D-jack RS232, 9-pin SUB-D-jack
Interface speed 300 bps - 115 kbps 1200 bps - 230 kbps 300 bps - 115 kbps 300 bps - 115 kbps
Interface to network Screw clamp and RJ-45 (Western) Screw clamp and RJ-45 (Western) FME-antenna jack 10Base-T on  RJ-45 (Western)

 

Physical features

 

Dimensions in mm (b x t x h) 55 x 110 x 75 55 x 110 x 75 55 x 110 x 75 55 x 110 x 75
LEDs 4 (Power, Off Hock, DCD, RX/TX) 4 (Power, Off Hock, DCD, RX/TX) 5 (Power, Off Hock, DCD, RX/TX, Signal) 4 (Power, Off Hock, DCD, RX/TX)
Mounting DIN-rail DIN-rail DIN-rail DIN-rail
Temperature range 0...55°C 0...55°C 0...55°C 0...55°C
Humidity 0-95% non-condensing 0-95% non-condensing 0-95% non-condensing 0-95% non-condensing

 

* 1)UL in preparation; 2)Support by GSM provider required; Subject to change without prior notice